Verification of energy reduction effect through control optimization of supply air temperature in VRF-OAP system

Je Hyeon Lee, Hyun Jin Yoon, Piljae Im, Young Hak Song

Research output: Contribution to journalArticlepeer-review

20 Scopus citations

Abstract

This paper developed an algorithm that controls the supply air temperature in the variable refrigerant flow (VRF), outdoor air processing unit (OAP) system, according to indoor and outdoor temperature and humidity, and verified the effects after applying the algorithm to real buildings. The VRF-OAP system refers to a heating, ventilation, and air conditioning (HVAC) system to complement a ventilation function, which is not provided in the VRF system. It is a system that supplies air indoors by heat treatment of outdoor air through the OAP, as a number of indoor units and OAPs are connected to the outdoor unit in the VRF system simultaneously. This paper conducted experiments with regard to changes in efficiency and the cooling capabilities of each unit and system according to supply air temperature in the OAP using a multicalorimeter. Based on these results, an algorithm that controlled the temperature of the supply air in the OAP was developed considering indoor and outdoor temperatures and humidity. The algorithm was applied in the test building to verify the effects of energy reduction and the effects on indoor temperature and humidity. Loads were changed by adjusting the number of conditioned rooms to verify the effect of the algorithm according to various load conditions. In the field test results, the energy reduction effect was approximately 15-17% at a 100% load, and 4-20% at a 75% load. However, no significant effects were shown at a 50% load. The indoor temperature and humidity reached a comfortable level.

Original languageEnglish
Article number11010049
JournalEnergies
Volume11
Issue number1
DOIs
StatePublished - 2018

Funding

Disclaimer: This effort was supported by Samsung Electronics and the U.S. Department of Energy. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe upon privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise, does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States Government or any agency thereof. The views and opinions of the authors expressed herein do not necessarily state or reflect those of the United States Government or any agency thereof. Acknowledgments: This work was supported by the National Research Foundation of Korea (NRF) grant funded by the Korea government (MSIP) (No. 2017R1A2B2006424). This manuscript has been authored by UT-Battelle, LLC, under Contract Number DE-AC05-00OR22725 with the U.S. Department of Energy. The United States Government retains and the publisher, by accepting the article for publication, acknowledges that the United States Government retains a non-exclusive, paid-up, irrevocable, world-wide license to publish or reproduce the published form of this manuscript, or allow others to do so, for United States Government purposes.

FundersFunder number
U.S. Department of Energy
Samsung
Ministry of Science, ICT and Future PlanningDE-AC05-00OR22725, 2017R1A2B2006424
National Research Foundation of Korea

    Keywords

    • Control algorithm
    • Energy savings
    • Experiment
    • Field test
    • Outdoor air processing unit (OAP)
    • Variable refrigerant system (VRF)

    Fingerprint

    Dive into the research topics of 'Verification of energy reduction effect through control optimization of supply air temperature in VRF-OAP system'. Together they form a unique fingerprint.

    Cite this