TY - JOUR
T1 - Steady-state analysis of maximum photovoltaic penetration levels on typical distribution feeders
AU - Hoke, Anderson
AU - Butler, Rebecca
AU - Hambrick, Joshua
AU - Kroposki, Benjamin
PY - 2013
Y1 - 2013
N2 - This paper presents simulation results for a taxonomy of typical distribution feeders with various levels of photovoltaic (PV) penetration. For each of the 16 feeders simulated, the maximum PV penetration that did not result in a steady-state voltage or current violation is presented for several PV location scenarios: clustered near the feeder source, clustered near the midpoint of the feeder, clustered near the end of the feeder, randomly located, and evenly distributed. In addition, the maximum level of PV is presented for single, large PV systems at each location. Maximum PV penetration was determined by requiring that feeder voltages stay within ANSI Range A and that feeder currents stay within the ranges determined by overcurrent protection devices. Generation ramp rates, protection and coordination, and other factors that may impact maximum PV penetrations are not considered here. Simulations were run in GridLAB-D using hourly time steps over a year with randomized load profiles based on utility data and typical meteorological year weather data. For 86% of the 336 cases simulated, maximum PV penetration was at least 30% of peak load.
AB - This paper presents simulation results for a taxonomy of typical distribution feeders with various levels of photovoltaic (PV) penetration. For each of the 16 feeders simulated, the maximum PV penetration that did not result in a steady-state voltage or current violation is presented for several PV location scenarios: clustered near the feeder source, clustered near the midpoint of the feeder, clustered near the end of the feeder, randomly located, and evenly distributed. In addition, the maximum level of PV is presented for single, large PV systems at each location. Maximum PV penetration was determined by requiring that feeder voltages stay within ANSI Range A and that feeder currents stay within the ranges determined by overcurrent protection devices. Generation ramp rates, protection and coordination, and other factors that may impact maximum PV penetrations are not considered here. Simulations were run in GridLAB-D using hourly time steps over a year with randomized load profiles based on utility data and typical meteorological year weather data. For 86% of the 336 cases simulated, maximum PV penetration was at least 30% of peak load.
KW - Distributed power generation
KW - photovoltaic (PV) systems
KW - power distribution
KW - power system simulation
UR - http://www.scopus.com/inward/record.url?scp=84875688860&partnerID=8YFLogxK
U2 - 10.1109/TSTE.2012.2225115
DO - 10.1109/TSTE.2012.2225115
M3 - Article
AN - SCOPUS:84875688860
SN - 1949-3029
VL - 4
SP - 350
EP - 357
JO - IEEE Transactions on Sustainable Energy
JF - IEEE Transactions on Sustainable Energy
IS - 2
M1 - 6357275
ER -