Abstract

The need for modern electricity infrastructures and more capable grid components brings attention to Distributed Series Reactor (DSR) technology because of its control capabilities. DSRs are a new smart grid technology that can be applied to control flows in transmission or distribution systems. Design of DSRs to control power flow over transmission lines to alleviate overloads due to load growth under single line contingencies is investigated in this paper. N-1 contingency analysis is performed to assure secure operation of the grid while controlling the active power flow. The IEEE 39 bus standard model is modified to a 3-phase, unbalanced transmission model with 345 kV lines that accounts for tower geometry. The design of DSRs to control power flow under N-1 line contingency is performed using this modified 3-phase, unbalanced model. DSR design to control the power flow of a real power system over tie lines connecting different power pool areas and to control the power flow over transmission lines within the area itself is investigated. The economics of DSRs are then evaluated by comparing the DSR design with a design that uses new line construction.

Original languageEnglish
Pages (from-to)223-231
Number of pages9
JournalElectric Power Systems Research
Volume136
DOIs
StatePublished - Jul 1 2016
Externally publishedYes

Funding

This research has been sponsored by the DOE ARPA-E GENI program , Smart Wire Grid , Electrical Distribution Design , and the Virginia Tech Middle East and North Africa (VT-MENA) .

Keywords

  • Distributed series reactor(DSR) design
  • Electric power transfer
  • Load growth
  • N-1 contingency analysis
  • Power flow control
  • Unbalanced transmission systems

Fingerprint

Dive into the research topics of 'Power flow control and N-1 contingency analysis with DSRs in unbalanced transmission networks'. Together they form a unique fingerprint.

Cite this