Low-Pressure Heat Transfer Fluids for Pumped Two-Phase Cooling

Nitin Karwa, Samuel Yana Motta

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

2 Scopus citations

Abstract

The increasing heat flux from chips, and high server- and rack-level heat densities in high performance computing infrastructure have resulted in the advent of advanced cooling technologies, such as cold plates and immersion cooling. Water-based heat transfer fluids are used in cold plate systems. It is widely debated if it will be effective and energy efficient for cooling of chips with heat flux exceeding 500 kW/m2. Two-phase cooling with dielectric fluorinated fluids, such as hydrofluorocarbons (HFC), hydrochlorofluoroolefins (HCFO), hydrofluoroolefins (HFO), hydrofluoroethers (HFE), in cold plates may be more suited to sustain the ever-increasing heat density. The need to cool devices with ever-increasing power density, the push towards lower global warming potential fluids, and the occupational and equipment safety requirements has motivated a search for suitable two-phase heat transfer fluids. This paper introduces the environmental and occupational safety aspects, and effect of global regulations on the selection of fluorinated heat transfer fluids for use in data centers. This study presents drop-in performance evaluation of low-pressure fluid options, namely, HCFO-1233zd (E), HFC-245fa and HFE-7000, in pumped two-phase cooling system for heat flux up to 640 kW/m2. Performance is also compared with single-phase water cooling. The performance is reported in terms of thermal resistances of the cold plate and the system. Compared to water cooling, two-phase cooling achieved lower junction temperatures and more uniform cooling at much lower flow rate. System level thermal resistance was lower for two-phase cooling, except with HFE-7000, which had considerably high thermal resistance in the condenser. Unlike HCFO-1233zd(E), HFC-245fa will be eventually phased-down globally, therefore it is not a sustainable long-term option for the industry. This study shows that HCFO-1233zd(E) is a feasible low-pressure heat transfer fluid option for thermal management of high performance computing infrastructure.

Original languageEnglish
Title of host publicationProceedings of the 20th InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITherm 2021
PublisherIEEE Computer Society
Pages188-196
Number of pages9
ISBN (Electronic)9781728185392
DOIs
StatePublished - 2021
Externally publishedYes
Event20th InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITherm 2021 - Virtual, San Diego, United States
Duration: Jun 1 2021Jun 4 2021

Publication series

NameInterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITHERM
Volume2021-June
ISSN (Print)1936-3958

Conference

Conference20th InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITherm 2021
Country/TerritoryUnited States
CityVirtual, San Diego
Period06/1/2106/4/21

Keywords

  • Environmental regulations
  • HCFO-1233zd(E)
  • HFC-245fa
  • HFE-7000
  • High performance computing
  • Low-pressure fluid
  • Microchannel cold plate
  • Occupational safety
  • Pumped two-phase cooling
  • Refrigerant
  • Thermal resistance
  • Water