Abstract
Hydropower units often rely on legacy excitation systems with fixed automatic voltage regulator (AVR) settings, but parameter drift, changing operating conditions, and evolving grid-service demands can degrade terminal-voltage regulation over time. This problem should be addressed because poor voltage regulation affects reactive-power support, system stability, and reliable plant operation, and replacing installed AVR and limiter logic is costly and disruptive in practice. To address this issue, this paper proposes a retrofit-friendly enhancement for hydropower generator excitation systems that combines adaptive tuning of the AVR middle lead–lag branch with a small proportional-integral correction for removing steady bias and slow drift. The adaptive laws are normalized, projection-bounded, and equipped with leakage, while adaptation is enabled only in the middle branch. Thus, the intent of the underexcitation and overexcitation limiters, as well as legacy current and rate limits, remains unchanged. Stability is analyzed under incremental performance assumptions, yielding boundedness and asymptotic tracking in the absence of saturation. The method is evaluated using real operational data from a utility-scale hydropower unit at Rocky Reach Dam, Unit C-8. Compared with the fixed AVR baseline, the proposed method reduces terminal-voltage mean squared error by about 70%, removes long periods of steady-state bias, and improves transient tracking while coexisting with limiter actions. These results show that substantial voltage-control improvement can be achieved on existing hydropower units with minimal integration effort and without replacing the installed AVR structure.
| Original language | English |
|---|---|
| Article number | 111966 |
| Journal | International Journal of Electrical Power and Energy Systems |
| Volume | 178 |
| DOIs | |
| State | Published - May 2026 |
Funding
This work was supported in part by UT–Battelle LLC, through the US Department of Energy (DOE) under Contract DE-AC05-00OR22725 ; and in part by DOE’s Water Power Technologies Office under the Development of a Digital Twin for Hydropower Systems . This manuscript has been authored by UT-Battelle, LLC, under contract DE-AC05-00OR22725 with the US Department of Energy (DOE) . The US government retains and the publisher, by accepting the article for publication, acknowledges that the US government retains a nonexclusive, paid-up, irrevocable, worldwide license to publish or reproduce the published form of this manuscript, or allow others to do so, for US government purposes. DOE will provide public access to these results of federally sponsored research in accordance with the DOE Public AccessPlan ( http://energy.gov/downloads/doe-public-access-plan ).
Keywords
- ESST5B model
- Excitation systems
- Hydro generators
- Power system stability
- Voltage regulation
Fingerprint
Dive into the research topics of 'Limiter-aware adaptive excitation control for hydropower generators with legacy voltage regulation systems'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver