Skip to main navigation Skip to search Skip to main content

Grid synchronization using fixed filtering with magnitude and phase compensation

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

1 Scopus citations

Abstract

This paper describes a grid synchronization technique for single phase systems using only fixed filtering and compensation networks. Compared with other phase locking techniques, the proposed approach has the advantage of requiring no feedback control and a simplistic and predictable design. The paper uses test scenarios and metrics described in IEEE C37-118.1 for testing phasor measurement units (PMUs) to evaluate the performance of the proposed method. The dynamic response of the proposed approach is compared with the second order generalized integrator phase locked loop (SOGI-PLL) and second order generalized integrator frequency locked loop (SOGI-FLL).

Original languageEnglish
Title of host publication2014 IEEE Energy Conversion Congress and Exposition, ECCE 2014
PublisherInstitute of Electrical and Electronics Engineers Inc.
Pages2641-2647
Number of pages7
ISBN (Electronic)9781479956982
DOIs
StatePublished - Nov 11 2014

Publication series

Name2014 IEEE Energy Conversion Congress and Exposition, ECCE 2014

Fingerprint

Dive into the research topics of 'Grid synchronization using fixed filtering with magnitude and phase compensation'. Together they form a unique fingerprint.

Cite this