Abstract
The resonant frequency of the LCL filter can drift away from its nominal value due to the circuit components parameters uncertainty and the grid-side impedance, which will further deteriorate the robustness of the system and damping performance. Conventional online resonant frequency estimation schemes, such as discrete Fourier transformation and recursive prediction error, require a significant amount of computational power to implement, which may even need to reduce the sampling and control frequency of the inverter controller. In this work, an extremum seeking control based resonant frequency estimation scheme is proposed, which can provide an accurate estimate of the resonant frequency with notably reduced execution time. Simulations, hardware-in-the-loop (HIL) tests, and experimental tests on a single-phase grid-tied inverter are conducted to validate the effectiveness of the proposed scheme.
| Original language | English |
|---|---|
| Title of host publication | 2021 IEEE Energy Conversion Congress and Exposition, ECCE 2021 - Proceedings |
| Publisher | Institute of Electrical and Electronics Engineers Inc. |
| Pages | 882-886 |
| Number of pages | 5 |
| ISBN (Electronic) | 9781728151359 |
| DOIs | |
| State | Published - 2021 |
| Externally published | Yes |
| Event | 13th IEEE Energy Conversion Congress and Exposition, ECCE 2021 - Virtual, Online, Canada Duration: Oct 10 2021 → Oct 14 2021 |
Publication series
| Name | 2021 IEEE Energy Conversion Congress and Exposition, ECCE 2021 - Proceedings |
|---|
Conference
| Conference | 13th IEEE Energy Conversion Congress and Exposition, ECCE 2021 |
|---|---|
| Country/Territory | Canada |
| City | Virtual, Online |
| Period | 10/10/21 → 10/14/21 |
Funding
This work was supported by the Oak Ridge National Laboratory (ORNL) funded through the Department of Energy (DOE) - Office of Electricity’s (OE), Transformer Resilience and Advanced Components (TRAC) program led by the program manager Andre Pereira.
Keywords
- LCL filter
- extremum seeking control (ESC)
- grid-tied inverter
- resonant frequency estimation