Experimental study of adiabatic capillary tubes: Critical flow of refrigerant/oil mixtures

S. F.Yana Motta, S. L. Braga, J. A.R. Parise

Research output: Contribution to journalArticlepeer-review

6 Scopus citations

Abstract

The critical flow of R-407C/oil mixtures through adiabatic capillary tubes is evaluated in this article. The available literature does not lead to definitive conclusions about the impact of oil on critical flow through capillary tubes. This phenomenon was studied experimentally using oil concentrations ranging from 2.9% to 7.9% (by mass), degrees of subcooling ranging from 8.1°C to 28.5°C (14.6°F to 51.3°F), and a condensing pressure of 1763 kPa (241 psia). The results obtained clearly show the trends of critical mass flow rate for several oil concentrations in the flowing fluid. The experimental data are analyzed and contribute to the knowledge of the influence of oil on the performance of adiabatic capillary tubes.

Original languageEnglish
Pages (from-to)331-344
Number of pages14
JournalHVAC and R Research
Volume7
Issue number4
DOIs
StatePublished - Oct 2001
Externally publishedYes

Funding

The present research work is based on the doctoral dissertation of Dr. Samuel F. Yana Motta. The authors are grateful to CAPES and the Brazilian National Agencies of Research (CNPq) for funding this project.

FundersFunder number
National Research Centre

    Fingerprint

    Dive into the research topics of 'Experimental study of adiabatic capillary tubes: Critical flow of refrigerant/oil mixtures'. Together they form a unique fingerprint.