Experimental Evaluation of Refrigerant Leak Characteristics for Different HVAC&R Equipment Types–Phase 2

  • Viral K. Patel
  • , Ahmad Abuheiba
  • , Jeff Chambers
  • , Ahmed Elatar
  • , Saad Jajja
  • , Van Baxter
  • , Viktor Reshniak

Research output: Other contributionTechnical Report

Abstract

The US Department of Energy (DOE) Building Technology Office (BTO) and the Air-conditioning, Heating & Refrigeration Technology Institute (AHRTI) collaborated to sponsor an experimental study of refrigerant leak characteristics at Oak Ridge National Laboratory (ORNL); AHRTI project 9012. The project has been conducted in two phases with objectives to conduct refrigerant leak tests on several heating, ventilating, air-conditioning and refrigeration (HVAC&R) systems under operating conditions representative of actual applications to document the pressure decay rate and the mass flow rate of leaked refrigerant as a function of time. Phase 1 of the project ran from late 2017 to late 2018 with refrigerant leaks imposed on five systems and the collection of data to meet the project objectives. Systems chosen covered three air-conditioning (AC) applications (packaged terminal AC or PTAC, 3-ton residential split system AC, and 5-ton packaged rooftop AC) and two refrigeration applications (split system unit cooler, and standalone display case). AHRTI members donated the test systems used for the project. The systems were tested at two different leak rates (catastrophic high rate simulating full line break and a lower flow rate), two leak locations (high-pressure side and low-pressure side), and two operating conditions (compressor ON or OFF). Phase 1 results were summarized in a project report by Baxter, et al. (2019)1. The leak rates imposed in Phase 1 led to much more rapid charge releases than the more typical much slower rates seen in practice that would take days, weeks, or months to empty a system of its entire charge. For Phase 2, the project sponsors asked that the “higher” leak rate target a total charge release time of about 4 min. This was intended to represent a “reasonable” worst case release scenario to match the refrigerant leak rate assumption used in the International Electrotechnical Commission (IEC) standard IEC 60335-2-40 (2016 version [IEC 2016]. A charge release time of about 20–40 min (leak release rate 5 to 10 times lower than higher rate) was targeted for the “lower” leak rate. This report provides a summary of the Phase 2 effort. Two additional HVAC systems were selected for testing in this phase. First was a multi-split air-conditioning (MS-AC) system with one outdoor section and two indoor units and a nameplate refrigerant charge of 1.75 kg (3.86 lb.) of R-410A. The MS-AC was tested in cooling only or AC operation. Second was a split system heat pump coupled to two different representative supply duct systems (HP-duct) and a nameplate charge of 3.83 kg (8.44 lb.) of R-410A. This system was tested in both space heating and AC modes. As in Phase 1 of the project, all tests were conducted using R-410A.
Original languageEnglish
Place of PublicationUnited States
DOIs
StatePublished - 2023

Keywords

  • 32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION
  • 42 ENGINEERING

Fingerprint

Dive into the research topics of 'Experimental Evaluation of Refrigerant Leak Characteristics for Different HVAC&R Equipment Types–Phase 2'. Together they form a unique fingerprint.

Cite this