TY - GEN
T1 - Control system for the ornl multicharged ion research facility high-voltage platform
AU - Bannister, M. E.
AU - Meyer, F. W.
AU - Sinclair, J.
PY - 2005
Y1 - 2005
N2 - A control system for the 250-kV platform and beamlines for accelerating and transporting ions produced by an all-permanent-magnet ECR ion source has been developed at the ORNL Multicharged Ion Research Facility. This system utilizes the Experimental Physics and Industrial Control System (EPICS) software to manipulate a programmable logic controller (PLC) and its associated I/O points. Additional control points are accessed by the EPICS Input/Output Controller (IOC) via RS-232 and GPIB interfaces. The Allen Bradley ControlLogix chassis located at each of the electrical potentials of the installation, that is at the source, platform, and ground potentials, are interconnected via Ethernet utilizing fiber optic transmission to bridge the different high voltage environments. The user interface for the EPICS IOC is built with the Extensible Display Manager (EDM) software. Performance of the control system during initial experiments using the high-voltage platform will be reported.
AB - A control system for the 250-kV platform and beamlines for accelerating and transporting ions produced by an all-permanent-magnet ECR ion source has been developed at the ORNL Multicharged Ion Research Facility. This system utilizes the Experimental Physics and Industrial Control System (EPICS) software to manipulate a programmable logic controller (PLC) and its associated I/O points. Additional control points are accessed by the EPICS Input/Output Controller (IOC) via RS-232 and GPIB interfaces. The Allen Bradley ControlLogix chassis located at each of the electrical potentials of the installation, that is at the source, platform, and ground potentials, are interconnected via Ethernet utilizing fiber optic transmission to bridge the different high voltage environments. The user interface for the EPICS IOC is built with the Extensible Display Manager (EDM) software. Performance of the control system during initial experiments using the high-voltage platform will be reported.
UR - http://www.scopus.com/inward/record.url?scp=33847107259&partnerID=8YFLogxK
U2 - 10.1109/PAC.2005.1591549
DO - 10.1109/PAC.2005.1591549
M3 - Conference contribution
AN - SCOPUS:33847107259
SN - 0780388593
SN - 9780780388598
T3 - Proceedings of the IEEE Particle Accelerator Conference
SP - 3591
EP - 3593
BT - Proceedings of the Particle Accelerator Conference, PAC 2005
T2 - Particle Accelerator Conference, PAC 2005
Y2 - 16 May 2005 through 20 May 2005
ER -